This page lists every formula and constant the calculators use. All of them live in one JavaScript file. The browser runs it on each page, and our automated tests run the same file before every release.

Room cooling

We take the ENERGY STAR room air conditioner chart (100 to 2,500 ft², 8 ft ceiling) as published and apply its rules: −10% for heavy shade, +10% for a very sunny room, +600 BTU/h for each regular occupant beyond two, and +4,000 BTU/h for a kitchen. One addition is ours: we scale by ceiling height ÷ 8. Where a range boundary appears in two rows of the chart, we treat each range as including its lower bound, so 150 ft² reads as 6,000 BTU/h. Above 2,500 ft², we scale the last row by area (13.6 BTU/h per ft²) and point you to the whole-house tool.

Heating load

Heating BTU/h = floor area × (ceiling ÷ 8) × UA × (70 °F − 99% design temperature)

The design temperatures are ASHRAE 2009 Fundamentals 99% heating dry-bulb values for one airport per zone, converted from °C and rounded:

ZoneStation99% heatingCooling BTU/ft² (avg.)
1Miami, FL52 °F30
2Houston, TX33 °F28
3Atlanta, GA26 °F25
4Baltimore, MD17 °F22
5Chicago, IL2 °F20
6Minneapolis, MN-8 °F18
7Duluth, MN-14 °F16
8Fairbanks, AK-38 °F16

UA is the whole-house heat loss coefficient per square foot of floor. We derived the "average" and "good" levels from a 2,000 ft² two-story reference house:

PartAverage houseGood (2010s code)
Walls (net of windows)1,300 ft² × U 0.09 (R-11 cavity)1,600 ft² × U 0.0625 (R-20 class)
Attic ceiling1,000 ft² × U 0.05 (R-19)1,000 ft² × U 0.026 (R-38)
Windows300 ft² × U 0.50 (double-pane)300 ft² × U 0.30
Floor / foundation≈ 70 BTU/h·°F≈ 50 BTU/h·°F
Air leakage0.018 × 16,000 ft³ × 0.7 ACH0.018 × 16,000 ft³ × 0.35 ACH
Total UA ÷ 2,000 ft²≈ 587 → 0.29, we use 0.30≈ 366 → 0.18, we use 0.20
0.018 BTU/ft³·°F is the heat capacity of air; ACH = air changes per hour.

The poor level (0.60) adds uninsulated walls, single-pane glass and about 1.2 ACH of leakage. The high-performance level (0.12) assumes R-49+ attic, R-20+5ci walls, U-0.27 windows and tight air sealing. The result is a design-day load with no safety margin. The page notes that ACCA Manual S lets furnace output run up to about 140% of it.

Whole-house cooling and tonnage

The load is floor area × the zone's cooling BTU per ft² × an envelope factor (1.20 / 1.00 / 0.85 / 0.70) × ceiling ÷ 8 × a sun factor (±10%). The per-ft² values are planning figures, not a Manual J. They put an average house at about 400 ft² per ton in zone 1 and 750 ft² per ton in zone 7, the span usually quoted by contractors. We then list every nominal size from 1.5 to 5 tons that is within ACCA Manual S's 90–115% of the load, and pick the one closest to 100%. A tie goes to the smaller unit.

Ducts

Round duct diameter comes from the fitted friction-chart equation for galvanized duct, Δp = 0.109136 Q1.9 / D5.02. Rectangular equivalents use the Huebscher equation, De = 1.30 (ab)0.625 / (a+b)0.25. Airflow defaults to 400 CFM per ton. For flex duct we recommend the next standard size up rather than pretend to model compression.

Insulation

R per inch uses one typical value per material, inside the published range, and the page always prints the range too. Wall assemblies use the ASHRAE parallel-path method with 25% framing by default, softwood at R-1.25 per inch, and standard surface films. Code tables are copied from 2021 IECC Table R402.1.3 and the ENERGY STAR retrofit table.

How we test

Found a wrong number?

Email [email protected] with the page, your inputs and what you expected. If we confirm the error, we fix it, add your case to the test suite and note the change on the page with a new date.